Home > Products > Automation > FLIR A310

FLIR A310

  • 0
  • Sunday March 6th, 2016

FLIR thermal imaging cameras go a step further by providing an early warning response to hot spots that are detected. This is important for all types of warehouses but in particular for those that contain contents that are prone to spontaneous combustion, or highly flammable.

a3101

A310 – Indoor


a3102

A310 -Outdoor

 

 

 

 

 

 

 

 

REQUEST FOR QUOTATIONREQUEST FOR MORE INFORMATION

 

Having introduced ultimate solutions that help in preventing fire incidents and disasters, in this section, WESAM offers solutions to identify “at an early stage” fire incident by using state-of-the-art automated thermal monitoring system (FLIR A310-series made in the USA) and trigger the necessary alarms and send necessary alerts to personal for immediate intervention before the actual fire takes place.

FLIR A310
Measurement analysis
Spotmeter 10
Area 10 boxes with max./min./average/position
Isotherm 1 with above/below/interval
Measurement option Measurement Mask Filter
Schedule response: File sending (ftp), email (SMTP)
Difference temperature Delta temperature between measurement functions or reference temperature
Reference temperature Manually set or captured from any measurement function
Atmospheric transmission correction Automatic, based on inputs for distance, atmospheric temperature and relative humidity
Optics transmission correction Automatic, based on signals from internal sensors
Emissivity correction Variable from 0.01 to 1.0
Reflected apparent temperature correction Automatic, based on input of reflected temperature
External optics/windows correction Automatic, based on input of optics/window transmission and temperature
Measurement corrections Global and individual object parameters
Alarm
Alarm functions 6 automatic alarms on any selected measurement function, Digital In, Camera temperature, timer
Alarm output Digital Out, log, store image, file sending (ftp), email (SMTP), notification
Ethernet
Ethernet Control, result and image
Ethernet, protocols Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP
Ethernet, image streaming 16-bit 320 x 240 pixels at 7-8 Hz-Radiometric

 

FLIR A300 / A310 – Standard FLIR A300f / A310f – Environmental housing
Environmental data
Operating temperature range –15°C to +50°C –25°C to +50°C
Encapsulation IP 40 (IEC 60529) IP 66 (IEC 60529)
Bump 25 g (IEC 60068-2-29) 5 g, 11 ms (IEC 60068-2-28)
Physical data
Weight 0.7 kg 4 kg
Camera size (L × W × H) 170 × 70 × 70 mm 460 × 140 × 150 mm
Tripod mounting UNC ¼”-20 (on three sides) N/A
Base mounting 2 × M4 thread mounting holes (on three sides) TBA
System features
Automatic heaters N/A Clears ice from window
Pan/tilt
Azimuth range N/A N/A
Elevation range N/A N/A
Programmable presets N/A N/A
Ethernet video streaming
Ethernet, video streaming MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5 MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5
Power system
External power operation 12/24 VDC (10-30 VDC), 24 W absolute max 12/24 VDC (10-30 VDC), 24 W absolute max
Consumption

 

Imaging and optical data
Field of view (FOV) / Minimum focus distance 25° × 18.8° / 0.4 m
Lens identification Automatic
Thermal sensitivity/NETD < 0.05°C at +30°C / 50 mK
Focus Automatic or manual (built in motor)
F-number 1.3
Image frequency 30 Hz
Zoom 1–8× continuous, digital, interpolating zooming on images
Detector data
IR resolution 320 × 240 pixels
Detector pitch 25 μm
Detector time constant Typical 12 ms
Focal Plane Array (FPA) / Spectral range Uncooled microbolometer / 7.5–13 μm
Measurement
Object temperature range –20 to +120°C0 to +350°C
Accuracy ±2°C or ±2% of reading
Set-up
Color palettes Color palettes (BW, BW inv, Iron, Rain)
Set-up commands Date/time, Temperature°C
Storage of images
Image storage type Built-in memory for image storage
File formats Standard JPEG, 16-bit measurement data included
Composite video
Video Composite video output, PAL and NTSC compatible
Video, standard CVBS (ITU-R-BT.470 PAL/SMPTE 170M NTSC)
Digital input/output
Digital input 2 opto-isolated, 10–30 VDC
Digital output, purpose As function of ALARM, Output to ext. device (programmatically set)
Digital output 2 opto-isolated, 10–30 VDC, max 100 mA
Digital I/O, isolation voltage 500 VRMS
Digital I/O, supply voltage 12/24 VDC, max 200 mA
Digital I/O, connector type 6-pole jackable screw terminal
Digital input, purpose Image tag (start/stop/general), Input ext. device (programmatically read)
Ethernet
Ethernet, standard IEEE 802.3
Ethernet, connector type RJ-45
Ethernet, type 100 Mbps
Ethernet, communication TCP/IP socket-based FLIR proprietary
Ethernet, video streaming MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5
Ethernet, power Power over Ethernet, PoE IEEE 802.3af class 0
Power system
External power operation 12/24 VDC, 24 W absolute max
External power, connector type 2-pole jackable screw terminal
Voltage Allowed range 10–30 VDC
Environmental data
Storage temperature range –40°C to +70°C
Humidity (operating and storage) IEC 60068-2-30/24 h 95% relative humidity +25°C to +40°C
EMC • EN 61000-6-2:2001 (Immunity)• EN 61000-6-3:2001 (Emission)• FCC 47 CFR Part 15 Class B (Emission)
Vibration 2 g (IEC 60068-2-6)
Physical data
Housing material Aluminium

Inquire more about FLIR A310.