Home > Products > Automation > FLIR A310 ex

FLIR A310 ex

  • 0
  • Sunday March 6th, 2016

Fully compliant with ATEX regulations
A310-ex

a310f3
Condition Monitoring
a310f2
Flare Detection
a310f1
Early Fire Detection

Use the power of thermal imaging in hazardous locations.

REQUEST FOR QUOTATIONREQUEST FOR MORE INFORMATION

 

Explosive atmospheres need to be protected from ignition sources by selecting equipment and protective systems which meet the requirements of the ATEX Product Regulations or similar regulations.
FLIR A310 ex is an ATEX compliant solution, with a thermal imaging camera mounted in an enclosure, making it possible to monitor critical and other valuable assets also in explosive atmospheres. Process monitoring, quality control and fire detection in potentially explosive locations are typical applications for the A310 ex.

1. Heater
2. Sensors for temperature, air humidity, voltage & pressure
3. Power supply: 24V DC
4. 2 SFP ports for fiber optic, 100 Base-FX or copper ethernet
5. ATEX compliant housing

Fixed mounted thermal imaging cameras like FLIR A310 ex can be installed almost anywhere to monitor your critical equipment and other valuable assets. It will safeguard your plant and measure temperature differences to assess the criticality of the situation. This allows you to see problems before they become costly failures, preventing downtime and enhancing worker safety

Learn more about the FLIR A310, the thermal imaging camera inside FLIR A310 ex.

General Data
Ambient temperature range for operation –20°C to +40°C (-4°F to 104°F)
Protection class IP67
Weight 6.7 kg (without camera and lens)
Empty volume 5.06 l
External dimensions (without sun shield) D = 170 mm, L = 408 mm
Housing material / Surface Nickel-plated aluminium / Powder coated
Protection window Germanium, double-sided AR Coated, externally with additional hard-carbon layer
Maximum power of the additional heater 16 W
Operating voltage 24 V DC
Maximum electric connection power 60 W
Power cable / Power cable configuration Helukabel 37264 / Pigtail
Length of power cable 4 m (13 ft.)
Integrated controller 4-port switch with 2 × fiber-optic LC 100Base-FX or 2 × RJ45(10/100) up-links, ring-topology support for reduced cabling effort, 2 × internal temperature sensors, air humidity and pressure sensor, digital output module controllable via Modbus TCP/IP or web interface to enable turning the heater on/off
Ethernet medium Multi-mode breakout fiber AT-V(ZN)Y(ZN)Y 4G50/125 OM2
Length of Ethernet cable 4 m (13 ft.)
Ethernet, configuration Pigtail with FC-connector
Explosion protection-specific data
For use in EX zone 1, 2, 21, and 22
Ignition protection category Flame-proof enclosure “d”
Maximum surface temperature (according to temperature class T6) Maximum 85°C
ATEX certification (version -AXC) EX-Protection Gas: II 2G Ex d IIC T6 Gb, EX-Protection Dust: II 2D Ex tb IIC T85° Db
Verification certificate ZELM 12 ATEX 0485 X
Imaging and optical data
IR resolution 320 × 240 pixels
Thermal sensitivity/NETD < 0.05°C @ +30°C (+86°F) / 50 mK
Field of view (FOV) / Focal length 25° × 18.8° with 18 mm (0.7 in.) lens or 45° × 33.8° with 9.66 mm (0.38 in.) lens
Minimum focus distance 0.4 m (1.31 ft.)
Spatial resolution (IFOV) 1.36 mrad with 25° lens or 2.59 mrad with 45° lens
Lens identification Automatic
F-number 1.3
Image frequency 30 Hz
Focus Automatic or manual (built in motor)
Zoom 1–8× continuous, digital, interpolating zooming on images
Detector data
Detector type Focal Plane Array (FPA), uncooled microbolometer
Spectral range 7.5–13 μm
Detector pitch 25 μm
Detector time constant Typical 12 ms
Measurement
Object temperature range –20 to +120°C (–4 to +248°F) 0 to +350°C (+32 to +662°F)
Accuracy ±2°C (±3.6°F) or ±2% of reading
Measurement analysis
Spotmeter 10
Area 10 boxes with max./min./average/position
Isotherm 1 with above/below/interval
Measurement option Measurement Mask Filter Schedule response: File sending (ftp), email (SMTP)
Difference temperature Delta temperature between measurement functions or reference temperature
Reference temperature Manually set or captured from any measurement function
Atmospheric transmission correction Automatic, based on inputs for distance, atmospheric temperature and relative humidity
Optics transmission correction Automatic, based on signals from internal sensors
Emissivity correction Variable from 0.01 to 1.0
Reflected apparent temperature correction Automatic, based on input of reflected temperature
External optics/windows correction Automatic, based on input of optics/window transmission and temperature
Measurement corrections Global and individual object parameters
Alarm
Alarm functions 6 automatic alarms on any selected measurement function, Digital In, Camera temperature, timer
Alarm output Digital Out, log, store image, file sending (ftp), email (SMTP), notification
Set-up
Color palettes Color palettes (BW, BW inv, Iron, Rain)
Set-up commands Date/time, Temperature°C/°F
Storage of images
Storage media Built-in memory for image storage
File formats Standard JPEG, 16-bit measurement data included
Ethernet
Ethernet Control, result and image
Ethernet, type / standard 100 Mbps / IEEE 802.3
Ethernet, configuration Pigtail with FC-connector (fiber)
Ethernet, communication TCP/IP socket-based FLIR proprietary
Ethernet, video streaming MPEG-4, ISO/IEC 14496-1 MPEG-4 ASP@L5
Ethernet, image streaming 16-bit 320 × 240 pixels @ 7-8 Hz – Radiometric
Ethernet, protocols Ethernet/IP, Modbus TCP, TCP, UDP, SNTP, RTSP, RTP, HTTP, ICMP, IGMP, ftp, SMTP, SMB (CIFS), DHCP, MDNS (Bonjour), uPnP

Inquire more about FLIR A310 ex.